Stand there through one full cycle before anything else, because when you hear it does the diagnosis. A single bang at the instant the pump shuts off is the check valve and water hammer, which is a completely different problem. Noise or shaking while the pump is running is this list.
And this list has unusually high stakes for a noise. The manufacturer gives three causes, and two of them have the same two-word remedy: replace pump.
Only the third is a part. “Piping attachments to building structure too rigid or too loose” — fixed with a rubber coupling. So the pipework is what you rule out first, not because it is most likely, but because it is the only outcome that is not a new pump.
The maker’s three causes

**From the troubleshooting chart, under “Pump operates noisily or vibrates excessively”:**
1. “Piping attachments to building structure too rigid or too loose“ — “Install rubber coupling (available at local hardware stores) to isolate pump vibration from discharge plumbing” 2. “Worn bearings” — “Replace pump“ 3. “Impeller broken” — “Replace pump“
Notice what the manufacturer does not offer. There is no bearing replacement, no impeller service, no adjustment. On a submersible sump pump those two faults are the end of the machine, and the maker says so in two words rather than describing a repair.
Which is why the order below is the order it is. Not by likelihood — the manual does not rank them — but by what each outcome costs you, and by which one you can investigate without touching anything electrical.
Start with the pipework, and read “or too loose” twice
The instinct when a pipe is shaking is to strap it down harder. The manufacturer names the opposite as an equal cause: “too rigid or too loose.”
Rigid means the pump’s vibration has a solid path into the building — the discharge pipe is strapped tight to a joist, and the joist becomes the thing making the noise.
Loose means a strap or hanger that has worked slack, letting the pipe knock against what it is fixed to. That is an observation about what a loose strap does mechanically, not something the manual explains — Wayne lists the cause without elaborating.
The published remedy is specific, and it is the one outcome here that is a part:
“Install rubber coupling (available at local hardware stores) to isolate pump vibration from discharge plumbing”
A manufacturer naming the part and where to buy it is unusual, and it tells you the fix is expected to be within reach.
One important distinction, because the same manual contradicts a careless reading of that line. It also says “Do not use flexible hosing” and “Do not use flex hosing in a permanent application.”
A short rubber coupling joining two rigid sections is not the same thing as running flexible hose as your discharge line. The first is the published remedy. The second is prohibited in the same document.
One-minute check, no tools: follow the discharge pipe from the pit to where it leaves the building and put a hand on every strap and hanger. You are looking for two things: a strap so tight the pipe and the joist are one object, and a strap loose enough to rattle.
What the pump is standing on
Also published, and also free to check:
“Do not place pump directly on clay, earth, gravel or sand. A brick or block must be installed under the pump to provide a solid base.”
A pump resting on silt at the bottom of a pit has no solid base, and a pump that can rock has somewhere to put its vibration.
This matters more in some pits than others. A manufactured basin has a moulded bottom; a site-formed concrete or earth pit may not, and years of silt can build a soft bed under a pump that started out level.
One-minute observation: look at how the pump sits. If it is not level, or if it has sunk into anything, that is both a noise cause and a wear cause — and it is on the manufacturer’s own list of things not to do.
If the pipework and the base are both fine
Then you are into the two causes that end with “replace pump.”
Worn bearings produce a noise that is constant whenever the motor is turning, mechanical in character, and gets worse rather than better. It does not change as the pit empties, because it is not about the water.
A broken impeller tends to be harsher and may come with a drop in how fast the pit clears — the pump is still spinning but no longer moving what it did.
Pro note on telling them from the pipework: a pipework noise changes when you touch the pipe. Put a hand firmly on the discharge line while it runs and see whether the character of the noise changes. A bearing does not care what you are holding.
And neither of these is a repair. The manufacturer’s warranty position and what these machines are realistically good for is its own question — but the short version is that a sump pump making a mechanical noise is a sump pump near the end of its service.
When it comes to replacing it, the specs that actually separate these pumps are a different question, and worth reading before the emergency rather than during it.
What this is not
It is not the bang at shutoff. That single knock as the pump stops is water hammer and the check valve, and nearly every article about it has the mechanism backwards.
It is not a pump that starts too often. Frequent starting is a cycling question rather than a noise one, even though it sounds like more noise.
And a brief hum at the moment of starting is normal on a motor of this kind. The symptom here is noise or vibration that persists while the pump is running.
When this needs a pro
Any work on the discharge pipework. Cutting in a coupling means opening a line that is under pressure when the pump runs, and a joint that fails on a discharge line fails during a storm.
Lifting the pump to check what it is standing on. It is wet, it is electrical, and the pit may be deeper than it looks.
Anything electrical at all, including moving the pump to a different position in the pit.
And deciding whether a mechanical noise means replacement now or replacement soon. If the pit, the pump and the discharge have never been assessed together, a new pump into the same installation may make the same noise.
What you can do yourself: listen through one full cycle and note whether the noise is a single bang or continuous, run a hand along the discharge pipe and its straps, and look at whether the pump is sitting level on something solid. Three observations, no tools — and they separate a hardware-store part from a new pump.
FAQ
Why is my sump pump noisy?
The manufacturer lists three causes: piping attachments to the building that are too rigid or too loose, worn bearings, and a broken impeller. Only the first has a remedy that is a part — a rubber coupling to isolate the pump’s vibration from the discharge plumbing. The other two say replace pump.
What is the difference between a banging sump pump and a vibrating one?
Timing. A single bang at the instant the pump shuts off is water hammer at the check valve, which has its own article. Noise or shaking that continues while the pump runs is a different list entirely, covering pipework, bearings and the impeller.
Can a loose pipe make a sump pump noisy?
Yes — the manufacturer names “too rigid or too loose” as one cause, which is worth noting because the instinct is to strap a shaking pipe tighter. A loose attachment lets the pipe knock against what it is fixed to; a rigid one gives vibration a solid path into the building.
Should a sump pump sit on the bottom of the pit?
Not directly on clay, earth, gravel or sand. The manual asks for a brick or block under the pump to provide a solid base. A pump that can rock or that has settled into silt has somewhere to put its vibration, and that is both a noise and a wear problem.
Can I use a flexible hose to stop sump pump vibration?
Be careful with that reading. The published remedy is a rubber coupling to isolate the pump from the discharge plumbing, while the same manual separately says not to use flexible hosing, and not to use flex hosing in a permanent application. A short coupling between rigid sections is not the same as a flexible discharge line.
Does a noisy sump pump need replacing?
If it is the pipework, no — that is a coupling. If it is worn bearings or a broken impeller, the manufacturer’s own remedy for both is replace pump, with no repair offered. Checking the pipe and the base first is what tells you which conversation you are having.